Importing the Fan Performance Data Table

Simcenter STAR-CCM+ calibrates the fan momentum source in your simulation with performance data from a real fan.

To provide this performance data:

Import the appropriate fan curve table into the simulation.

Shown below is a simplified example of a fan performance data table. The two columns are volumetric flow rate, Vol, in cubic meters per second (m^3/s), and pressure rise, Press, in Pascals (pa):

Vol Press
0.01 458.58
0.20 286.26
0.40 267.68
0.60 239.05
0.80 220.56
1.00 190.52
1.20 146.84
1.40 98.86
1.60 46.45
1.80 -27.10
2.00 -111.15
2.20 -204.01

Ensure that the pressure decreases with increasing flow rate across the fan for all data points in the table. If you use a fan curve that does not meet this requirement, the results are unstable.